Hey all.
Zone 2 (Phoenix, AZ)
Roof overhang, 16″
Just got told by a County rep that she wants,
SHEET #A3.0: Call out the size of each roof drain and scupper. Design shall be based on 6” rainfall in 1 hour. Provide emergency overflow drain(s). Overflow drains having the same size as the roof drains shall be installed with the inlet flow line located 2 inches above the low point of the roof, or overflow scuppers having three times the size of the roof drains and having a minimum opening height of 4 inches shall be installed in the adjacent parapet walls with the inlet flow located 2 inches above the low point of the roof served. Typical throughout. (2018 IRC R903.4 and R903.4.1)
The draftsman shows a 4” parapet on the plans. With the length of the cricket, the parapet wall would have to be ~8” or taller…is my math crazy? I’m considering removing the cricket all together and making the parapet 2” tall thus eliminating the need for an “overflow drain.”
If I do make the parapet 2”, is there guidance or code that suggests how far apart scuppers should be? The total length of the roof pictured is ~60ft with scuppers on each end.
Also, how the heck do I figure how big the drain must be for 6” of rainfall in 1 hour?
TIA, Paul